Board of Adjustment Meeting
Regular MeetingWest Valley City, UT · July 6, 2016
Minutes
WEST VALLEY CITY
BOARD OF ADJUSTMENT
MINUTES
July 6, 2016
The meeting was called to order at 6:01 p.m. by Necia Christensen at 3600 Constitution
Boulevard, West Valley City, Utah.
WEST VALLEY CITY BOARD OF ADJUSTMENT MEMBERS
Necia Christensen, Russell Moore, and Scott Spendlove
WEST VALLEY CITY PLANNING DIVISION STAFF
Steve Lehman and Brenda Turnblom
WEST VALLEY CITY LEGAL DEPARTMENT:
Brandon Hill
AUDIENCE
Approximately four (4) people were in the audience.
Board of Adjustment
Page 2
B-5-2016
Central Valley Water Reclamation Facility - Variance
2212 West 2890 South
M Zone
REQUEST:
The Central Valley Water Reclamation Facility (CVWRF) is requesting a variance from the West
Valley City Code. Section 7-6-1104(1) requires that all buildings be set back a minimum distance
of 25 feet from any private or public road. The applicant is requesting a variance of 13.89 feet in
order to install a ferric chloride storage and chemical feed system within a new building. The
property is located at approximately 2212 West 2890 South and is zoned manufacturing.
BACKGROUND:
� The subject property is known as Parcel 15-28-226-002. The property is owned by Granger
Hunter Improvement District. At the present time, Granger Hunter operates a sewer lift
station at this location.
� According to the applicant, in October 2014 CVWRF experienced a catastrophic failure in
a cement mortar lined and coated 30-inch siphon barrel which conveyed sanitary sewer
flows from GHID to the Central Valley regional wastewater treatment facility.
� As work commenced to fix the problem, it was determined that the pipe soffit had
completely deteriorated due to hydrogen sulfide. While the work to fix the pipeline has
been completed, the work did nothing to prevent the formation of the Hydrogen Sulfide
gasses. These gasses are toxic, and are being transferred downstream to other locations.
In a letter to the Board, the applicant explains the ramifications of this gas if not treated.
� The applicant explains that Hydrogen Sulfide gas may be effectively controlled through
the addition of iron salt chemicals such as ferric chloride. The CVWRF believes the
introduction of this chemical will prevent a future failure as happened in 2014.
� The CVWRF is proposing to install a new building from which to manage the introduction
of the ferric chloride. The new building will be located on a portion of property owned by
GHID. Due to the function and existing infrastructure of this station, including access in
and through the site, the only location to place this building is along the western portion of
the site.
� Section 7-6-1104(1) of the City Code requires that the minimum building setback be 25
feet from all public or private streets. The proposed building will be setback a distance of
11.11 feet, thus requiring a variance of 13.89 feet.
Board of Adjustment
Page 3
� The applicant has provided a letter outlining the problem which has caused the need for
the variance. Maps detailing the future location of the new building have also been
provided. To address the variance criteria, the applicant has also provided answers to the
5 questions.
� Should the Board of Adjustment approve the variance, the applicant will be required to
submit a conditional use application and construction plans to the City for the new building.
� ORDINANCE SUMMARY:
Section 7-6-1104(1) of the West Valley City Land Use Development and Management Act
requires that the minimum building setback be 25 feet from all public or private streets.
The West Valley City Land Use Development and Management Act Section 7-18-107
outlines the standards or conditions for approving a variance. The Board of Adjustment
may grant a variance only if:
1. Literal enforcement of the zoning ordinance would cause an unreasonable hardship for
the applicant that is not necessary to carry out the general purpose of the zoning
ordinance.
2. There are special circumstances attached to the property that do not generally apply to
other properties in the same zoning district.
3. Granting the variance is essential to the enjoyment of a substantial property right
possessed by other property in the same zoning district.
4, The variance will not substantially affect the general plan and will not be contrary to
the public interest.
5. The spirit of the zoning ordinance is observed and substantial justice done.
According to Williams, American Land Planning Law (Volume 5, Criteria for the Validity of
Variances, pages 131 and 133 et.seq.) There is a presumption against granting a variance and it
can only be granted if each of the standards are met.
In Wells v. Board of Adjustment of Salt Lake City, the Utah Court of Appeals held that a Board’s
decision to grant a variance would be illegal if the required statutory findings were not made.
Applicants:
Thomas A. Holstrom
Central Manager, Central Valley Water Reclamation Facility
800 West Central Valley Road
Board of Adjustment
Page 4
Salt Lake City, UT 84119
Dr. Phil Heck
Assistant General Manager and Process Engineer
Kevin Gallagher
Engineering Technician
Discussion: Necia Christensen disclosed that she is president of the Utah Association of
Special Districts of which the Central Valley Water Reclamation Facility (CVWRF) is a
member. She does not believe that will have any impact on the decision that is made
tonight.
Thomas Holstrom said this facility is in response to a significant infrastructure failure
that occurred October 6, 2014. CVWRF accepts flows from Granger/Hunter Water
Improvement District. The average flow is almost 12 million gallons per day to the
CVWRF treatment facility. Nearly all flow passes through pump stations; one of them is
the Decker Lake Pump Station. The flow is conveyed through a double barrel siphon
structure that carries these flows beneath the Jordan River eastward to the CVWRF
treatment facility. One of the barrels collapsed in October 2014. Upon excavation and
exposure, it was learned that the pipe system had incurred severe corrosive attack from
hydrogen sulfide. Because these sewer gasses cannot travel underwater, they were
trapped at the syphon in the structure and deteriorated the pipe system. This was quite a
safety issue. This collapse was adjacent to an apartment complex and immediately
adjacent to the Utah Cultural Celebration Center. Hydrogen sulfide not only can corrode
these types of facilities, but there is also a strong odor emitted. You will recognize the
rotten egg odor. Once CVWRF repaired this system, these corrosive and odorous gasses
are now being entrained in the flow and conveyed downstream to our treatment facility.
This has created an access issue at the headworks where crews are now having to don
self-contained breathing apparatus in order to enter the screen room to do routine
maintenance.
Thomas Holstrom confirmed hydrogen sulfide can also escape at manhole locations. He
mentioned he is surprised that the apartment complex next to the Granger/Hunter Lift
Station hasn’t experienced some odor problems. This facility will serve to address both
corrosion and odor issues from the point of injection all the way to the CVWRF treatment
facility.
Thomas Holstrom read his responses to each of the five criteria for granting a variance:
1. As shown in our drawings the proposed chemical storage / chemical feed system is
placed just inside the fence line of the GHID Decker Lake Pump Station, but within the
20 foot setback. This is the only known location on the site that can accommodate a
reasonably sized chemical storage tank which will preclude excessively frequent and
Board of Adjustment
Page 5
costly low volume chemical deliveries. Minimum bulk chemical deliveries are at 4000
gallons and come by way of tanker truck. The GHID Pump Station site is designed for
truck deliveries by way of a drive-through ingress / egress on the site. Placement of the
chemical tank at the shown location will allow for offloading of chemical and direct
departure of the truck from the site. Other locations within and around the GHID Pump
Station building cannot be accessed by the tank truck due to limited truck turning radius.
The proposed project includes a structure that matches the architectural treatments of the
pump station building. Landscaping of an approximate ten foot corridor, immediately
south of the proposed project, is included. The matching structure and landscaping
features should adequately carry out the general purpose of the zoning ordinance.
2. The GHID Decker Lake pump station property includes a public utility installation to
pump sanitary sewage to the CVWRF interceptor system for conveyance to the regional
treatment plant. The pump station meets critical public health and safety needs of the
surrounding community.
3. Allowing placement of the chemical feed facility as shown will result in efficient delivery
of chemical and its introduction into the sanitary sewage pumping station. Granting the
variance to allow for this facility will result in reduction of hydrogen sulfide gasses and
the resultant odors caused by them. Odor and corrosion control at this site is essential to
the enjoyment of adjacent property holders and residents and to the protection of
downstream piping.
4. CVWRF believes that the granting of the variance will result in a facility that is in
concert with the use of the remaining GHID property and is essential to the public health
and enjoyment of surrounding properties, which is important to realization of the General
Plan. Granting of the requested variance to allow for this chemical feed facility is clearly
in the public interest.
5. CVWRF believes that the proposed architectural treatments and landscaping will be
adequate to meet the spirit of the zoning ordinance even with the variance allowed to the
20 foot setback requirement. CVWRF firmly believes that the public health, safety
and enjoyment benefits represented by this chemical feed facility will more than
offset any zoning ordinance compromise represented by the requested variance.
CVWRF, its member entities and patrons, including thousands who reside in the West Valley
City / Granger-Hunter Improvement District areas, respectfully hope for your considered
granting of this variance request to allow this important project to proceed.
Scott Spendlove asked if ferric chloride is currently being stored on this site. Thomas
Holstrom answered no, not at this time. Scott Spendlove asked if the ferric chloride will
be in liquid form. Thomas Holstrom answered yes. Scott Spendlove asked if all proper
safety, ingress, and egress issues will be addressed with this being so close to a
Board of Adjustment
Page 6
residential area. Brandon Hill confirmed, as part of the conditional use process, hazmat
permits will be issued through the fire department and proper access will be addressed.
Dr. Phil Heck acknowledged the reason for the building is to provide a protective
structure around the tank. The substructure of the building is a containment structure that
contains more than the volume of the tank. It is coated with a protective coating that is
resistant to ferric chloride. Ferric chloride is not explosive or corrosive, but it is acidic
and needs to be contained within the structure. There is a safety shower in the building to
meet OSHA requirements.
Necia Christensen closed the public portion of the meeting.
Motion: Scott Spendlove moved to approve B-5-2016.
Russell Moore seconded the motion.
Necia Christensen feels anything we can do protect our neighbors and keep the sewer
utility properly working is something we can do. All commissioners agreed the criteria
for the variance were very well thought out and presented in a reasonable manner.
A roll call vote was taken:
Necia Christensen Yes
Russell Moore Yes
Scott Spendlove Yes
Motion Carries - B-5-2016 Continued – Unanimous
OTHER
Approval of June 1, 2016 Minutes – Approved
There being no further business, the meeting adjourned at 6:27 p.m.
Brenda Turnblom, Administrative Assistant
Agenda
WEST VALLEY BOARD OF ADJUSTMENT MEETING
WEST VALLEY CITY HALL
3600 SOUTH CONSTITUTION BOULEVARD
COUNCIL CHAMBERS
Wednesday, July 6, 2016
Board of Adjustment Meeting..................................................................................... @ 6:00 p.m.
VARIANCES
B-5-2016 The CENTRAL VALLEY WATER RECLAMATION FACILITY is requesting a
variance from the West Valley City Code. Section 7-6-1104(1) requires that all buildings
be set back a minimum distance of 25 feet from any private or public road. The applicant
is requesting a variance of 13.89 feet in order to install a ferric chloride storage and
chemical feed system within a new building. The property is located at approximately
2212 West 2890 South and is zoned manufacturing. (Staff - Steve Lehman at 801-963-
3311)
OTHER
Approval of Minutes from June 1, 2016
West Valley City does not discriminate on the basis of race, color, national origin, sex, religion, age or disability in employment or the provision of services.
If you are planning to attend this public meeting and, due to a disability, need assistance in understanding or participating in the meeting, please notify the City eight or more
hours in advance of the meeting. We will try to provide whatever assistance may be required. The person to contact for assistance is Brenda Turnblom, 963-3282.
Get email alerts for West Valley City
A daily email when new agendas and minutes are posted.