Board of Code Appeals
Regular MeetingSterling Heights, MI · September 8, 2016
Minutes
BOARD OF CODE APPEALS
REGULAR MEETING
September 8, 2016
SUBJECT: The minutes of the Board of Code Appeals meeting of September 8 , 2016.
The meeting was called to order by Chairman Stanek at 6:03 pm
MEMBERS PRESENT: Douglas Harvey, Laurel Johnson, Terry Measel,
Thaddeus Stanek, Thomas Szatkowski
Michael Viazanko, Building Official
RECORDING SECRETARY: Dana Vietto
APPROVAL OF AGENDA
Motion by Measel, supported by Johnson, to approve the agenda as presented.
Yes: All Absent: None. Motion: Carried.
CONSIDERATIONS
1. Recreating Recreation Video Shown
2. PG16-0198 – Chrysler Group , LLC (Michael Serdiuk -NSA Architects) - 38111 Van
Dyke
Requesting Board Approval for a variance to 1) Elimination of fire suppression in
electrical substations 2) Eliminate heat & smoke vents 3) Delete strobes from fire alarm
4) Eliminate sprinklers in ovens, wet scrubber tanks, below convey or over main fork
truck aisles, electrostatic paint zones and plastic paint tunnels 5) Eliminate fire alarm
monitoring, tamper switches and exterior riser alarms 6) Manual evacuation in lieu of
alarms 7) Allow travel distance to exceed 250 feet 8) Install large hose drops by egress
doors only 9) Eliminate fire alarm and fire suppression in new enclosed test track
addition.
Board has received correspondence from the Architect, Mr. Serdiuk. This was dated
August 18, 2016 which details the requests for the variances. The Board also received
a package of information on August 19, 2016. The following people were present
tonight; Ben Monacelli, manager for the building for FCA Group, Neal Wainstock,
Corporate Fire, Eric Goedtel, Project Manager for FCA Group, Jeff Faitel, representing
the insurance carriers for FCA Group, Michael Serdiul, NSA Architects, Chris Kulka,
paint project manager. They presented a power point presentation.
Motion by Harvey, supported by Johnson, to approve PG16-0198 at 38111 Van Dyke,
1)Fire suppression in Electrical Substation Rooms- The existing facility currently has
electrical substations located in the Penthouse level enclosed with a secured fenced
area that is not sprinkled. The existing substations are being replaced with new low
voltage switchgear and dry type (oil free) transformers. NFPA 13 allows an un-sprinkled
dedicated electric room with dry-type equipment. The existing wet fire suppression
system is being replaced with a higher density system throughout the building including
the penthouse with the exception of the areas directly about the electrical Substation
gear. Side shields will be installed at the heads at the perimeter of the electrical
equipment area to prevent the spray of water onto the electrical gear. FCA typically
does not have fire suppression in any of its electrical substation rooms. The rooms will
have smoke detectors and they will be monitored 24/7.
Yes: All Absent: None. Motion: Carried
Motion by Johnson, supported by Szatkowski, to approve PG16-0198 at 38111 Van
Dyke,
2)Smoke and Heat vents and Draft Curtains: Elimination of smoke and heat vents and
draft curtains. FCA proposes to use the facility ventilation system to evacuate heat and
smoke per Sterling Heights Fire Department command. This complies with the protocol
used in at the North Paint Shop and other similar manufacturing facilities.
Yes: All Absent: None. Motion: Carried
Board of Code Appeals Page 2
September 8, 2016
Regular Meeting
Motion by Szatkowski, supported by Harvey, to approve PG16-0198 at 38111 Van
Dyke,
3)Strobes: Delete use of strobes in areas under 85 dba in the plant environment. FCA
does not have any strobes in any of its manufacturing facilities in the US, as they have
been found to be confusing and not readily understood. The use of speakers does
follow established FCA plant protocol, and has been found to be effective and
understood. Strobes are used as indicators for the production line. Speakers and
strobes will be provided in office and employee service areas.
Yes: All Absent: None. Motion: Carried
Motion by Harvey, supported by Measel, to approve PG16-0198 at 38111 Van Dyke,
4)Sprinklers in Ovens: No sprinkler protection within ovens associated with spray
painting lines based upon: a) Welded seam wall construction b) Combustion safeguards
on gas train meets NFPA 68 with all components U.L. Listed c) No plastic components
on vehicle larger that fuel filler cap d) No masking paper or tape on vehicles.
Yes: All Absent: None. Motion: Carried
Motion by Measel, supported by Johnson, to approve PG16-0198 at 38111 Van Dyke,
5)Sprinklers in Eliminator (wet scrubber) Tanks: No sprinklers in eliminator tanks
(scrubber tanks) based upon constant wet conditions in a corrosive atmosphere.
Yes: All Absent: None. Motion: Carried
Motion by Szatkowski, supported by Johnson, to approve PG16-0198 at 38111 Van
Dyke,
6)Fire Protection below Conveyor over Main Fork Truck Aisles: No sprinkler protection
in main aisles below screen quarding and solid platforms since storage of combustible
materials not allowed in any aisle ways. Automatic sprinkler protection would be
provided at ceiling level.
Yes: All Absent: None. Motion: Carried
Motion by Harvey, supported by Szatkowski, to approve PG16-0198 at 38111 Van
Dyke,
7)Delete sprinkler protection in electrostatic paint spray zones in booths: A high speed
deluge system with pilot sprinklers being provided
Yes: All Absent: None. Motion: Carried
Motion by Harvey, supported by Johnson, to approve PG16-0198 at 38111 Van Dyke,
8)Delete sprinklers from plastic paint tunnels: Plastic Tunnel enclosures are to be 6 mil
unreinforced sheeting with non-combustible framing consistent with the North Paint
Shop. In case of fire the plastic sheeting will melt away and fall out of the framing
system
Yes: All Absent: None. Motion: Carried
Motion by Szatkowski, supported by Johnson, to approve PG16-0198 at 38111 Van
Dyke,
9)Fire Alarm System Monitoring: Provide “on-site” monitoring of fire protection system in
liew of direct reporting to a Central Stations. System will be monitored 24/7 by an onsite
Security vendor. First response will be by on-site personnel to verify condition. Once
the condition is evaluated, “911” will be alerted if required.
Yes: All Absent: None. Motion: Carried
Motion by Harvey, supported by Johnson, to approve PG16-0198 at 38111 Van Dyke,
10)Tamper Switches: Delete sprinkler control valve tamper switches and monitoring
(valves will be locked)
No: Measel Absent: None. Motion: Carried
Board of Code Appeals Page 3
September 8, 2016
Regular Meeting
Motion by Measel, supported by Johnson, to approve PG16-0198 at 38111 Van Dyke,
11)Exterior riser alarms: All risers are alarmed and report to the on-site fire alarm panel
monitored by a 24/7 security vendor. Access to the site is through a controlled access
point. The location of the alarmed riser will be communicated by the security staff to
arriving fire fighters.
Yes: All Absent: None. Motion: Carried
Motion by Szatkowski, supported by Measel, to approve PG16-0198 at 38111 Van
Dyke,
12)Manual evacuation: Building evacuation during an event will be a manual system to
eliminate false alarms. Building evacuation will be ordered as necessary.
Yes: All Absent: None. Motion: Carried
Motion by Harvey, supported by Szatkowski, to approve PG16-0198 at 38111 Van
Dyke,
13)Allow a travel distance in excess of 250 FT for a F-1 Occupancy: a) Per the MBC
1016.1 the allowable travel distance for Group F-1 occupancy is 250 feet. As shown on
the attached exiting plan (drawing G-100 the actual maximum travel distance based on
the current aisle layout approaches 600 feet. Relief is sought on the basis of the
following items: b) Timed exit studies at similar facilities have been commissioned by
FCA to show that the plant population will have adequate time to evacuate the facility
before the level of the smoke reaches the occupants due to the interior heights of the
facility. The height of the deck at this facility is an average of 30FT above finish floor. c)
The actual occupant load is currently estimated at 50 persons per shift. d) The facility is
a limited access facility. All of the people working in the facility receive training to
instruct them on the evacuation procedures for the facility. e) All visitors to the facility
have to view a training video prior to being permitted access to the facility and are
escorted by a FCA employee on site. f) Security monitors all visitors to the facility. g)
The ceiling sprinklers provided in the plant exceed the density required by NFPA. h)
The plant maintains a 24/7 security force on site. i) The fire alarm system at the plant is
a Class A monitored 24/7. j) The plant conducts an evacuation system test on each shift
every month. k) The plant conducts an evacuation drill yearly where all employees and
visitors are evacuated from the plant.
Yes: All Absent: None. Motion: Carried
Motion by Szatkowski, supported by Johnson, to approve PG16-0198 at 38111 Van
Dyke,
14)Locate Hose Drops at Egress Doors only 2 ½”: a) A waiver to section 905 of the MBC
is requested to eliminate the provision of hose drop connections throughout the facility.
Fire hose drops will be provided at man doors located around the perimeter of the
facility. b) The ceiling sprinklers provided in the plant exceed the density required by
NFPA c) Locations in the interior of the plant are occupied by process equipment which
will hinder access to the hose drop. d) Fire extinguishers will be located in accessible
locations around the facility. e) The plant maintains a 24/7 security force on site. f) The
fire alarm system at the plant is a Class A monitored 24/7.
Yes: All Absent: None. Motion: Carried
Motion by Measel, supported by Szatkowski, denied PG16-0198 at 38111 Van Dyke,
15)Delete the requirement to provide a fire alarm system in the new vehicle test track
enclosure. The proposed test track is a low speed test track to test vehicle performance
on variable road surfaces and steering wheel centering. The presence of strobes in the
facility would be a distraction to the driver of the vehicle. Similar facilities have not been
equipped in the past with a fire alarm system. The only occupants in the test track
enclosure are the drivers in the vehicles under normal operating conditions. The facility
will be equipped with air quality sensors and alarms to detect and warn of elevated
levels of vehicle emissions and may be confused with fire alarm strobes and alarms.
No: All Absent: None. Motion: Denied
Board of Code Appeals Page 4
September 8, 2016
Regular Meeting
Motion by Johnson, supported by Szatkowski, table to October13, 2016 meeting for
PG16-0198 at 38111 Van Dyke,
16)New Test Track Building Fire Protection: Delete the requirement to a fire suppression
system in the new vehicle test track enclosure. A new vehicle test track is being
constructed to replace the existing enclosed test track to accommodate the new vehicle
line to be produced at the plant. The test track is a low speed track with road test
surfaces. The construction of the building will be pre-engineered steel construction and
concrete pavement, with no combustible materials. Vehicles will be driven through the
test track at the rate of and average of one per minute. At any given time 3 to 6 vehicles
may be on the track. The track is required to be enclosed and connected to the
assembly building to meet the new testing standards. The building will be ventilated and
un-tempered with the exception of the area adjacent to the existing building. The
request follows the FCA internal fire protection protocols, and is supported by FCA’s
insurance carriers.
Yes: All Absent: None. Motion: Carried
OLD BUSINESS
None
NEW BUSINESS
None
PARTICIPATION
None
APPROVAL OF MINUTES
Motion by Measel, supported by Stanek, to approve the minutes of August 11, 2016.
Yes: All Absent: None. Motion carried.
ADJOURNMENT
Motion by Johnson, supported by Stanek, to adjourn.
Yes: All Absent: None. Motion carried.
Meeting adjourned at 8:25 pm.
Respectfully submitted,
Thaddeus Stanek
Thaddeus Stanek
Chairman
Agenda
CITY OF STERLING HEIGHTS
NOTICE OF PUBLIC HEARING
A regular meeting of the Board of Code Appeals is scheduled to be held at the
Sterling Heights Municipal Center, 40555 Utica Road, Sterling Heights, Michigan,
586-446-2360 on Thursday, September 8, 2016 at 6:00 p.m. The meeting
will be held in room #201 (Council Conference Room).
1. Call to Order
2. Roll Call
3. Approval of Agenda
4. Considerations
1. PG16-0198 – Chrysler Group, LLC (Michael Serdiuk-NSA Architects)
Requesting Board Approval for a variance to 1) Elimination of fire
suppression in electrical substations 2) Eliminate heat & smoke vents
3) Delete strobes from fire alarm 4) Eliminate sprinklers in ovens, wet
scrubber tanks, below convey or over main fork truck aisles, electrostatic
print zones and plastic paint tunnels 5) Eliminate fire alarm monitoring,
tamper switches and exterior riser alarms 6) Manual evacuation in lieu of
alarms 7) Allow travel distance to exceed 250 feet 8) Install large hose
drops by egress doors only 9) Eliminate fire alarm and fire suppression in
new enclosed test track addition.
Property address: 38111 Van Dyke
5. Old Business
6. New Business
7. Audience Participation
8. Approval of Minutes
August 11, 2016
9. Adjournment
ANY QUESTIONS REGARDING THE ABOVE ITEMS SHOULD BE DIRECTED TO
THE BUILDING SERVICES DIVISION 586-446-2360.
THE CITY OF STERLING HEIGHTS WILL PROVIDE NECESSARY REASONABLE
AUXILIARY AIDS AND SERVICES TO INDIVIDUALS WITH DISABILITIES AT THE
MEETING UPON 7 DAYS NOTICE TO THE COMMUNITY RELATIONS OFFICE AT
586-446-2489.
THIS MEETING WILL BE HELD IN ROOM #201
PLEASE ENTER AT THE NORTH ENTRANCE DOORS